Skip to content
Over 6000 Products at Incredible Prices!
Over 6000 Products at Incredible Prices!

Hager JK101SPD 125A Surge Protection Kit Type I/II

SKU JK101SPD
Original price £374.98 - Original price £374.98
Original price
£374.98 inc VAT £312.48 exc VAT
£374.98 - £374.98
Current price £374.98 inc VAT £312.48 exc VAT inc VAT £312.48 exc VAT

Estimated delivery time: Estimated delivery tomorrow*

Description

A Surge protection device (SPD) kit specifically developed for Hager standard TPN (Type B) Distribution boards. Developed to ensure optimal performance of SPD technology within Hager distribution boards. SPD is CT2 type to ensure compatibility with all common UK Earthing arrangements e.g. TN-C-S (PME), TN-S and TT earthing arrangements. This is an IEC Type 1/2 / class I/II SPD for 3 – phase power supply networks. A type 1 SPD is generally used in the primary board.

 

This SPD kit fits within the standard distribution board. Line, Neutral and Earth connections are via copper busbar and copper links, minimising SPD conductor losses, maximising the effective performance of the SPD (Up effective).

Specification
  • Colour - Light grey
  • European directive WEEE - Concerned
  • Nominal voltage Un - 230 / 400 V AC (TN / TT)
  • Nominal frequency fn - 50 Hz (60 Hz)
  • Maximum continuous operating voltage Uc (L-N) - 335 V AC
  • Maximum continuous operating voltage Uc (L-PE) - 235 V AC
  • Maximum continuous operating voltage Uc (N-PE) - 260V AC
  • Residual current lPE - ≤ 5 uA
  • Standby power consumption Pc - ≤ 360 mVA
  • Impulse discharge curr. IImp (10/350) μs L-N / N-PE - 12,5 kA / 50 kA
  • Nominal discharge current In (8/20) μs - 20kA
  • Maximum discharge current lmax (8/20) μs - 50kA
  • Follow current interrupt rating lfI (N-PE) - 100A
  • Short-circuit current rating lsccR - 25kA
  • Voltage protection level Up (L-N) - ≤ 1.35kV
  • Voltage protection level Up (L-PE) - ≤1.6 kV
  • Voltage protection level UP (N-PE) - ≤ 1.5kV
  • Max. backup fuse - 160 A (gG)
  • Max. backup fuse with V-type through wiring - 80 A (gG)
  • Standards/regulations - IEC 61643-11 2011 EN 61643-11 2012
  • IEC test classification - T1/2 I/II
  • EN type - T1/2 I/II
  • Mode of protection : L-N/ L-PE/  N-PE
  • Mounting type - DIN rail: 35 mm
  • Degree of pollution - 2
  • Overvoltage category - III
  • Degree of protection - IP20
  • Shock (operation) - 25g (Half-sine / 11 ms / 3x ±X, ± Y, ±Z)
  • Vibration (operation) - 5g (10 ... 500 Hz/ 2.5 h / X, Y, Z)

Datasheet